One rack, every cylinder
Cylinder-bank manifolds for inert gas systems: headers, check valves, flex connections, discharge test ports. Assembled and pressure-proofed on our bench — your site sees bolt-up only.
Data
| Duty | EN 15004 inert flooding systems |
|---|---|
| Pressure | 300 bar rated, 450 bar proof |
| Materials | 316 stainless headers, gunmetal valves |
| Testing | Nitrogen proof + leak-down logged |
| Scale | 2–20 cylinders, expansion kits |
Full declaration of performance and test evidence available with every shipment. Where a variant is listed, specify it in your RFQ.