The fire service plugs in here
Street-side inlet cabinet for dry risers: double breeching inlet, autodrain, and a marked red door the fire service can find at 3 a.m. with a torch. Built to BS 9990 duty.
Data
| Standard | BS 9990 system duty, EN 671-3 components |
|---|---|
| Inlets | 2 × 2½ in female instantaneous |
| Valves | Landing valves per floor, autodrain at inlet |
| Cabinet | 3 mm steel, RAL 3000, cylinder lock |
| Signage | BS 5499 FIRE INLET marker plate |
| Test | Hydraulic 15 bar proof, 10 bar working |
Full declaration of performance and test evidence available with every shipment. Where a variant is listed, specify it in your RFQ.