Short-circuit isolator plus monitored input for doors, dampers, extinguishing releases. When the loop is damaged, the isolator splits it into live halves — the panel keeps talking to both.

Data

Specification

Specification sheet — JD-IF2
ComplianceEN 54-18 (isolator)
Inputs1 monitored line, 47 kΩ EOL
OutputsVoltage-free SPDT relay, 30 V 1 A
SupplyLoop-powered, 24 V DC nominal
Current300 µA standby
AddressingOn-device rotary, 1 loop address
Mounting35 mm DIN rail or box mount
ProtectionIP21 housing standard

Full declaration of performance and test evidence available with every shipment. Where a variant is listed, specify it in your RFQ.